  1. If this is a service entrance conductor that's carrying the entire load of the service and if there are no derating issues at play, then you only need to size the wire at 83% of the load. In effect, a 100-amp service only needs to have 83-amp service entrance wires. That makes #2 AL THW a perfectly valid choice.
    1 point
  2. Occasionally, I'll see stainless steel piping.
    1 point
×
×