  1. An electrical panel cannot be used as a raceway, therefore, if the splices are to carry the conductors from the main panel to the sub-panel they should be removed from the main panel, put into a splice box and then extended to the sub-panel. Jimmy Filingeri Maple Ridge Consulting, LLC Hopeweel Junction, New York
  2. It does appear that the panel is an indoor panel used in an outdoor application. I would also be concerned about all of the splices in the panel box which is not allowed. It also appears that the phases are not properly color coded. Jimmy Filingeri Maple Ridge Consulting, LLC Hopewell Junction, New York
×
×