  1. Steve, to add more confusion to your question. The grounded conductor is not always a "neutral". This photo is of a corner grounded delta 3 phase panel. The white marked wires on the "neutral bar" are actually grounded phase conductors for this 3 phase system. It is required to be marked white per code because it is a "grounded conductor". It however, is not a neutral. It supplies the third leg of this system to power 3 phase equipment. Just thought I'd share. Corner grounded delta photo.docx
  2. The conductors appear to be the same size. This would be an issue if one is AL. (lower ampacity rating)
×
×