Jump to content

kasterko

Members
  • Content Count

    17
  • Joined

  • Last visited

Community Reputation

0 Neutral

About kasterko

  • Rank
    New Member

Personal Information

  • Location
    USA
  • Occupation
    Home Inspector
  1. How about an opposite situation. The treads were replaced and the nosing trim sticks up about 1/4" . This makes it an uneven stair tread with a little stop. It could also be a trip hazard depending on foot size. Wish I had a pic but the nosing is like a transition piece that's a little thicker than the tread.
  2. I came across this on new construction. It allows the owners to measure their electrical usage. I'm speaking of the 2 white metering devices on the service entrance cables and the leads exiting the panel at the bottom. I saw something similar to this befoe in a condo where they were trying to meter by individual units and I thought I was told it was wrong. I've searched the forum for "low voltage in panel" and found references to 110 and 725 and I'm still confused. I guess we'll be seeing more of this in our quest for energy efficiency I sent this before finishing and I wanted to know if the
  3. Any help on determining the age of a Burnham oil boiler model RS-112, ser- 35044173, Thanks,
  4. A 1950's home. This panel box is being used as a subpanel. The fuses are labeled as controlling the furnace, pump, "appl" and "gar/disp". This panel is feed, by what looks like SE cable, from a newer 150 main service panel with breakers. This subpanlel has no grounding wires in it. The junction box picture (poor) is where one of the circuits from the subpanel connects to a romex cable feeding the furnace and the grounding wire from the romex is connected to the junction box with a small green metal clip. The junction box was not grounded to anything I could see. I'm pretty sure disposals, furn
  5. I believe this has been discussed before. I tried searching and couldn't find anything. So, I ask, humbly - do most home inspectors test for gas leaks: under what conditions; and, how? I came across something recently that made me think about this for some reason. Maybe I take this for granted more than I should. I thinking about natural gas and propane and appreciate any guidance. Thanks in advance for any guidance.
  6. Thanks guys. Enjoy the holidays Oh, Other than aesthetics, I guess there's no reason not to have a boiler and W/H in the kitchen
  7. I was a taken back when I saw the HVAC unit and water heater installed in the kitchen, a first for me. I checked the IRC and I believe I found the places they could not be, which didn’t include a kitchen. So, are there any technical or safety type reasons not to install these units in a kitchen? Also, I’m having trouble determining the age of the Sears/Dunkirk boiler (series PW41 Model 229 963440 Serial 29830015). Thanks in advance. Image Insert: 559.52 KB
  8. In Three months meaning the 2008 NEC? Are GFCI requirements changing too? I've heard some thngs about AFCI's being required in more places. I guess we'll all need to be up on he new stuff fairly quickly.
  9. Now I'll really have to show my ignorance. I don't think it had a bypass duct. It had a humidifier(it wasn't on) in the only return I saw and I don't recall seeing anything that looked like what might be a bypass duct. I saw all 4 zone dampers on the supplies, nothing on returns (that I saw). I will get a humidity tester for future problems like this. The zones didn't operate properly. For example when only zone 1 should have been cooling, zone 4 was also cooling. I'm not sure why this house was zoned anyway, especially 4 zones, 2 on each floor of a 2 story 2600 sq. ft. house. I did recommend
  10. High humidity in new 2600 sq. ft. 2-story home on a crawlspace (6 months old) with A/C running normally (65-70% Rh as indicated on t-stat) also feels very muggy and supposedly T-stat humidity reading was compared to 2 other humidity meters and compared. So we’ll assume the humidity reading is correct. The Heat Pump condenser unit is a Carrier model 25HPA324300, serial 2206E22576. From what I can find out this is a 13 SEER, 2006 model and I think the 24 may indicate 2 ton (puron). The air handler is also a carrier model 58MXB080-F-10116, serial 3405A09316, with propane backup located in
  11. Mike, While I'm downloading the mega-document, what is the basic story on 203K inspections. A test, grandfathered by being a member of an association or society? Thanx,
×
×
  • Create New...